47
MASTERYS BC 100-120 kVA - Ref.: IOMMASBCXX07-EN 05
ENGLISH
10. TECHNICAL SPECIFICATIONS
1. 360 V with Pout = 90% Pn.
2. Initial Condition Pout ≤ 80% Pn
3. @ Battery Fully Discharged. Call SOCOMEC support service.
4. @ Battery Fully Charged. Call SOCOMEC support service.
Models 100 120
Electrical specifications - Input
Mains voltage Vin 3Ph+N 400 V -15% +20% (up to -40% @ 50% of nominal load)
Input frequency Hz 50-60 ±10%
Input power factor 0.99
THDI < 3%
Electrical specifications - External battery
Battery voltage range V bat from +/- 180
3
up to +/- 302
4
from +/- 190
3
up to +/- 302
4
Electrical specifications - Output
Output voltage V 3Ph+N 380/400/415 V ±1%
1
Frequency Hz 50-60 Hz ±0,2%
Automatic bypass 400 V ±15% (selectable from 10% to 20% if generator is used)
Nominal power kW 90 108
Overload
(@ 25 °C; Vin >
380; Vbat > 240)
2
• 10 minutes
• 1 minute
kW
112,5
135
135
162
Crest factor ≥ 2.7
Voltage distortion < 1% with linear load; < 4% with non-linear load
Environment
Operating temperature °C 0÷35 (15÷25 recommended)
Storage temperature °C -5÷45
Relative humidity % up to 95%
Max. altitude m 1000
Acoustic noise dBA < 65
Required cooling capacity m
3
/h 2000
Dissipated power max W 5299 7136
Dissipated power max BTU/h 18,091 24,362
Standards
Safety EN 62040-1/A1, EN 60950-1
Type and performance EN 62040-3 (VFI-SS-111)
EMC EN 62040-2 (Category C3)
Product certifi cation CE - TÜV-SÜD
Protection level IP20; IP21 on request
Mechanical characteristics with standard batteries
Dimensions (LxPxH) mm 700 x 830 x 1925
Weight kg 400