2. UNPACKING AND INSTALLATION OF THE UNIT
2.3. ENVIRONMENTAL REQUIREMENTS
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or sources of excessive heat.
The recommended operating temperature, humidity and altitude values are listed in the technical specifi cations table (see chapter 10).
Cooling systems may be required to maintain these values.
• The UPS must be installed in an environment with no obstructions and which is dry, clean and dust-free.
Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or chemical solutions).
The UPS can be installed against a wall; the distance will depend on the cables present. The upper part of the UPS must be
positioned at least 40 cm away from the ceiling (fi gure 2.3-1).
The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the front of the UPS
for maintenance purposes (fi gure 2.3-1).
For UPSs set up front-wise, leave a minimum space of 210 cm between the two cabinets so as to allow a passageway when
both doors are open (in accordance with standard IEC 60364 - see fi gure 2.3-1).
≥ 40 cm
≥ 210 cm
between the doors
UPS UPS
Several cabinets can be installed adjacent to each other (fi gure 2.3-2).
Two MASTERYS BC 100-120 systems can be installed back to back (fi gure 2.3-3).
Observe the direction of ventilation fl ows (fi gure 2.3-4) and heat dispersion fl ows (fi gure 2.3-5). See chapter 10 for the technical
specifi cations relating to required ventilation values.
≥ 10 cm *
UPS
BATTERY
CABINET
BATTERY
CABINET
UPS UPS UPS
* between the backs