55EN
MASTERYS GP4 60-160 kVA - Ref.: IOMMASGPXX07-EN 05
Configuration 1 STANDARD configuration (default)
IN/OUT DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE STATE
IN1 UPS POWER OFF 1 Command sent to UPS
(2)
Close to activate Normally open
IN2 GEN SET ON 1 Activate S023 status Open to activate Normally closed
IN3 INSULATION FAULT 10 Activate A026 Open to activate Normally closed
RELAY 1 GENERAL ALARM 10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2 OPERATING ON BATTERY 30 Relating to A019 Normally open
RELAY 3
END OF BACK-UP TIME 10 Relating to A017 Normally open
IMMINENT STOP 10 Relating to A000 Normally open
RELAY 4
LOAD SUPPLIED BY AUTO-
MATIC BYPASS
10 Relating to S002 Normally open
Configuration 2 OPTIONS SUPERVISOR configuration
IN/OUT DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE STATE
IN1 UPS POWER OFF 1 Command sent to UPS
(2)
Close to activate Normally open
IN2 FAN FAILURE 10 Activate A054 Close to activate Normally open
IN3 BATTERY DISCONNECTED 10 Activate A016 Open to activate Normally closed
RELAY 1 GENERAL ALARM 10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2 OPERATING ON BATTERY 30 Relating to A019 Normally open
RELAY 3 REDUNDANCY LOST 10 Relating to A006 Normally open
RELAY 4 BATTERY DISCONNECTED 1 Relating to A016 Normally open
Configuration 3 SAFETY configuration
IN/OUT DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE STATE
IN1 UPS POWER OFF 1 Command sent to UPS
(2)
Close to activate Normally open
IN2 INSULATION FAULT 1 Activate A026 Open to activate Normally closed
IN3 CHARGER DISABLE/ENABLE 10 Command sent to UPS
(2)
Open to activate Normally closed
RELAY 1 GENERAL ALARM 10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2 UPS POWER OFF 1 Relating to A059 Normally open
RELAY 3
END OF BACK-UP TIME 10 Relating to A017 Normally open
IMMINENT STOP 10 Relating to A000 Normally open
RELAY 4 INSULATION FAULT 1 Relating to A026 Normally open
Configuration 4 ENVIRONMENTAL configuration
IN/OUT DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE STATE
IN1 UPS POWER OFF 1 Command sent to UPS
(2)
Close to activate Normally open
IN2 PROGRAMMABLE ALARM 10 Activate A064 Open to activate Normally closed
IN3
BATTERY TEMPERATURE
ALARM
10 Activate A020 Open to activate Normally closed
RELAY 1 GENERAL ALARM 10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2
BATTERY TEMPERATURE
ALARM
10 Relating to A020 Normally open
RELAY 3 REDUNDANCY LOST 10 Relating to A006 and A001 Normally open
RELAY 4 PROGRAMMABLE ALARM 10 Relating to A064 Normally open
Configuration 5 EXTERNAL MAINTENANCE BYPASS configuration
IN/OUT DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE STATE
IN1 UPS POWER OFF 1 Command sent to UPS
(2)
Close to activate Normally open
IN2 GEN SET ON 1 Activate S023 status Open to activate Normally closed
IN3
EXTERNAL MAINTENANCE
BYPASS CLOSED
10 Activate S018 status Open to activate Normally closed
RELAY 1 GENERAL ALARM 10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2 OPERATING ON BATTERY 30 Relating to A019 Normally open
RELAY 3
END OF BACK-UP TIME 10 Relating to A017 Normally open
IMMINENT STOP 10 Relating to A000 Normally open
RELAY 4
LOAD SUPPLIED BY AUTO-
MATIC BYPASS
10 Relating to S002 Normally open
1. The acronyms mentioned are linked to MODBUS table (Snnn=Status/Annn=Alarm).
2. A self-locking emergency push button must be used for the UPS Power Off input.
Note: custom configuration is also available. For more information contact Socomec.