OFYS RT 1 - 3kVA - 551906A - SOCOMEC
19EN
• 04: ECO enable/disable
Interface Setting
Parameter 3: Enable or disable ECO function
You may choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
• 05: ECO voltage range setting
Interface Setting
Parameter 2 & 3: Set the acceptable high voltage point and low voltage
point for ECO mode by pressing Down key or Up key
HLS: High loss voltage in ECO mode in parameter 2.
The setting range in parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
The setting range in parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
• 06: Bypass enable/disable in stand-by mode
Interface Setting
Parameter 3: Enable or disable Bypass function:
You may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default).
• 07: Bypass voltage range setting
Interface Setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable
low voltage point for Bypass mode by pressing the Down key or Up key
HLS: Bypass high voltage point.
230-264: setting the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac).
LLS: Bypass low voltage point.
180-220: setting the low voltage point in parameter 3 from 180Vac to
220Vac. (Default: 180Vac).