12. MAINTENANCE
WARNING!
The UPS generates HAZARDOUS INTERNAL VOLTAGES. All maintenance operations should be carried out by
AUTHORISED SERVICE ENGINEERS ONLY.
The unit will operate to its maximum capability if kept powered round the clock (24/7); this ensures that the batteries will
always be properly charged.
If the appliance is not to be used for any length of time wait until the batteries are fully charged (connection to mains
power supply for 8 hours continuous) before shutting the UPS down.
Recharge the batteries for a duration of 24 hours at least every 4 weeks when the unit is not in use.
12.1. Storage
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25 °C ambient temperature) has
been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement
battery packing material.
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage,
recharge the battery in accordance with the following table:
Storage temperature Recharge frequency Charging duration
-25°C to 40°C Every 3 months 1-2 hours
40°C to 45°C Every 2 months 1-2 hours