OFYS RT 1 - 3kVA - 551906A - SOCOMEC
5EN
2. SAFETY STANDARDS
This user manual species installation and maintenance procedures, technical data and safety instructions for SOCOMEC.
For further information visit the Socomec website: www.socomec.com.
NOTE!
Any work carried out on the equipment must be performed by skilled, qualied technicians.
NOTE!
Before carrying out any operations on the unit read the installation and operating manual care- fully. Keep this
manual safe for future reference.
NOTE!
The models are not available for all markets. Contact Socomec for further information.
DANGER!
Failure to observe safety standards could result in fatal accidents or serious injury, and damage equipment or
the environment.
CAUTION!
If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing,
contact SOCOMEC. Do not operate the unit if it has suffered a violent mechanical shock of any kind.
NOTE!
Install the unit in accordance with clearances in order to prevent access to handling devices and guarantee
sufcient ventilation (refer to ‘Environmental requirements and handling’ chapter).
NOTE!
Only use accessories recommended or sold by the manufacturer.
NOTE!
When the equipment is transferred from a cold to a warm place wait approx. two hours before putting the unit
into operation.
NOTE!
When carrying out electrical installation, all standards applicable specied by the IEC, in particu- lar IEC
60364, and the electricity supplier must be observed. All national standards applicable to batteries must be
observed. For further information refer to ‘Technical specications’ chapter.
CAUTION!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should
be observed when working on batteries:
- Remove watches, rings or metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of the batteries.
- Disconnect the charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of grounded battery can result in electrical shock. The likelihood of such shock
can be reduced if such grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
WARNING!
Connect the protective earth (PE) conductor before making any other connections.
DANGER! RISK OF ELECTRIC SHOCK!
Before carrying out any operations on the unit (cleaning and maintenance performances, connection of
appliances, etc.) disconnect all power sources.
DANGER! RISK OF ELECTRIC SHOCK!
After disconnecting all power sources wait approx. 5 minutes for the complete discharge of the unit.
NOTE!
The UPS may be powered from an IT distribution system with a neutral conductor.