OFYS RT 1 - 3kVA - 551906A - SOCOMEC
18 EN
8.4. Menu function descriptions
There are three parameters to set up the UPS. Refer to following diagram.
Parameter 3Parameter 2
Parameter 1
Parameter 1: It’s for program alternatives. Refer to below
program list for the details.
Parameter 2 and parameter 3 are the setting options or
values for each program.
01: Output voltage setting
Interface Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac (power derating 70%)
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac
02: Frequency converter enable/disable
Interface Setting
Parameter 2 & 3: Enable or disable converter mode
You may choose the following two options:
CF ENA: converter mode enable (power derating 70%, transfer to bypass is
forbidden).
CF DIS: converter mode disable.
03: Ouput frequency setting
Interface Setting
Parameter 2 & 3: Output frequency setting
You may set the cold start frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following output
frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz