08: Autonomy limitation setting
Interface Setting
Parameter 3: Set up backup time on battery mode for general outlets
0-999: setting the backup time in minutes from 0-999 for general outlets on
battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled.
(Default).
09: Total battery AH
Interface Setting
Parameter 3: Set up total battery AH value of the UPS. (unit: AH)
7-999: setting the total battery capacity from 7 to 999. Please set up this
figure if external battery pack is connected.
If the UPS is standard model, the default setting is 9AH. If the UPS is long-run
model, the default setting is 65AH.
8.5. Fault code
Fault event Fault code Icon Fault event Fault code Icon
Bus start failure 01 None Inverter output short 14
Bus over 02 None Battery voltage too high 27
Bus under 03 None Battery voltage too low 28
Bus unbalance 04 None Over temperature 41 None
Inverter soft start failure 11 None Overload 43
High Inverter voltage 12 None Charger failure 45 None
Low Inverter voltage 13 None