Cross-Sectional Area (mm ²)
External Cable
Diameter(mm)
Step 1 Remove cable glands from the positive and negative
connectors.
Step 2 Remove the insulation layer with an appropriate length
from the positive and negative power cables by using a wire
stripper as show in Figure 4-5.
Figure 4-5 Connecting DC input power cables
1.Positive power cable 2.Negative power cable
Note: L2 is 2 to 3 mm longer than L1.
Step 3 Insert the positive and negative power cables into
corresponding cable glands.
Step 4 Insert the stripped positive and negative power cables into
the positive and negative metal terminals respectively and crimp
them using a clamping tool. Ensure that the cables are crimped
until they cannot be pulled out by force less than 400 N, as shown
in Figure 4-6.