SOFAR 1~4KTL2-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 31 -
Figure 4-9 NOT allowed: connect loads between inverter and circuit
breaker
Table 4-2 Recommended AC output cable specifications
Multi core copper wire
AC cable should be correctly sized to
ensure the power loss in AC cable is less
than 1% of the rated power. If the
resistance of the AC cable is too high, it
will cause a huge increase in the AC
voltage, which may lead to a
disconnection of the inverter from the electrical grid. The
relationship between power loss in AC cable and wire length, wire
cross sectional area is shown in the following figure
Figure 4-10 wire length, wire cross sectional area and wire power loss
Model
SOFAR
1.1KTL2-G3
SOFAR
1.6KTL2-G3
SOFAR
2.2KTL2-G3
SOFAR
2.7KTL2-G3
SOFAR
3KTL2-G3
SOFAR
3.3KTL2-G3
SOFAR
4KTL2-G3
Cable(Copp
er)
4mm²
4mm²
4mm²
6mm²
6mm²
6mm²
8mm²
Breaker
16A/400
V
16A/400
V
25A/400
V
25A/400V
25A/400V
25A/400
V
25A/400
V