Figure 4-9 NOT allowed: connect loads between inverter and circuit
breaker
Table 4-2 Recommended AC output cable specifications
Multi core copper wire
AC cable should be correctly sized to
ensure the power loss in AC cable is less
than 1% of the rated power. If the
resistance of the AC cable is too high, it
will cause a huge increase in the AC
voltage, which may lead to a
disconnection of the inverter from the electrical grid. The
relationship between power loss in AC cable and wire length, wire
cross sectional area is shown in the following figure:
Figure 4-10 wire length, wire cross sectional area and wire power loss