Sol-Ark Battery Integration Guide | SK140-0026-005 19
Communications Installation and Setup Instructions
Custom RJ45 cable (outdoor-rated inverters only)
Battery-IDs and connections
No custom cable is needed.
Battery IDs and connections
1. Configure the proper pin assignments of the LYNK II header board for Sol-Ark per the manufacturer's
manual.
2. Daisy-chain all modules (if in parallel) together using CAT5e or higher cables between LYNK ports.
3. Connect the LYNK port of a battery at one end of the chain to the LYNK port of the LYNK II.
If using the SLIMLINE enclosure, follow the manufacturer instructions for connecting the LYNK ports
and the LYNK II.
4. Download and use the LYNK ACCESS software from the Discover Battery website to configure the
LYNK II with the pre-configured Sol-Ark protocol.
Inverter programming and connections
1. Connect the cable between the LYNK II "CAN" port and the inverter's "Battery CANBus" port (outdoor
only).
2. Power on the battery stack by first switching the breaker to the ON (closed) position, then briefly
pressing the Power button to the ON position. If in parallel, turn on the Power Button first, then switch
the breakers to the ON position.
If using the SLIMLINE enclosure, follow the manufacturer instructions for turning on the battery stack.
3. Program the inverter with this battery's appropriate charge/discharge settings.
4. Enable “BMS Lithium Batt” and set its value to “00.”
5. (Optional) Turn on “BMS_Err_Stop” if you if you want the system to fault on battery communications
loss.