EndurEnergy ESP-5100
Follow these instructions for setting up EndurEnergy batteries and Sol-Ark inverters.
Be sure to consult the comprehensive technical documentation provided by EndurEnergy for
specifications and settings to ensure optimal performance and safety. Visit the manufacturer’s website
and consult the relevant documentation below.
EndurEnergy documentation
Communications Installation and Setup Instructions
Custom RJ45 cable
No custom cable is needed.
Battery IDs and connections
1. Connect all EndurEnergy ESP-5100 batteries together with the provided RJ45 cable using “M/S” ports.
(Can use up to 8 batteries in 48V low voltage configuration)
2. Set all the dip switches according to the battery manual and double-check all dip switches on all
batteries in the battery bank.
Inverter programming and connections
1. Connect a standard CAT5/6 cable to the “Inverter” port on the ESP-5100 Master battery, and the
“Battery CANBus” port (or the “CAN” port for indoor-only models) on the Sol-Ark.
2. Program the inverter with the appropriate charge/discharge settings according to the specific battery
manual and cable arrangement.
3. Enable “BMS Lithium Batt” and set its value to “00”.
4. (Optional) Turn on “BMS_Err_Stop” if you want the system to fault on the loss of battery
communications.