L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
Voltage window (At
100%/50% load)
-20%, +25% (166-260Vac or 176-275Vac), Full load
-40%, +25% (125-260Vac or 132-275Vac) , <50% Load
Power Walk IN(S) for parallel
system
Standard with busbar configuration as single feed
Battery block flexibility
Optional Voltage: ±96/108/120/132/144/156Vdc (16-26pcs
optional)
192Vdc~312Vdc (16~26pcs, 20 pcs define, 20~ 26pcs no
power derating; 18pcs output power factor 0.9;16pcs output
power factor 0.8;)
Battery temperature
compensation (standard /
optional)
40℃/104°F>T>25℃/ 82.4 °F , -7~0mV/℃,default:no
compensation
Manual and automatic programmable by time or voltage
110% 60mins, 125% 10mins, 150% 1mins
110% 60mins, 125% 10mins, 150% 1mins