EasyManua.ls Logo

SolarEdge L10US-IB20 - Page 75

SolarEdge L10US-IB20
79 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
Model
L10US
L15US
L20US
THDU
Linear load
2%
Non-linear
load
5%
Output PF
1
Output voltage
208/220Vac (3Ph+N+PE)
Static regulation of output
±1%
Slew rate -Maximum
frequency variation
0.5~2Hz/s
Bypass source voltage
windows setup and
Frequency windows setup
Frequency±10%±5%, ±4%, ±2%, ±1%
Upper limit: +10%, +15%, +20% or 25% (default: +25%)
Lower limit: -10%, -15%, -20%, -30% or -40% (default: -40%)
Output voltage
compensation (support
downstream transformer)
-5%~+5%
Output rate current
28/26A
42/39A
56/53A
System Features
Cooling
Cooling type
(heat pipe,
liquid, air)
Air
Air flow
input /
output
Air inlet: front
Air outlet: rear
Breaker
Internal
Mains
50A 3P
63A 3P
80A 3P
Internal
bypass
50A 3P
63A 3P
80A 3P

Table of Contents