NOTE
If changing the Export TH and Import TH default values, make sure
they sum up to a value that equals or greater than the appliance Load
Rating value. Otherwise, the device will turn off when there is
insufficient power to divert to the appliance.
Min ONTime - (optional); the minimum duration (in minutes) the appliance
should remain ONonce switched on, even when no excess PVpower is
available. The default value is 5 minutes.
3.
Select Use Excess PV. The following screen is displayed:
S e t < Y e s >
W e e k D a y s < 1 2 3 4 5 6 7 >
Set <Yes/ No> - automatically divert the excess PV to the device (default: Yes).
Week Days <optional> - days to repeat the settings (default: every day).
4.
Select Add Schedule. The following screen is displayed, showing schedule setting
options. You can configure up to four different schedules.
S m a r t S a v e
S c h e d u l e
D i s a b l e
R e m o v e S c h e d u l e
Use Disable to deactivate a schedule or Remove Schedule to delete it.
5.
Select and set one of the scheduling options:
Smart Save:
S e t < S m a r t >
R e a d y b y < 0 0 : 0 0 >
D u r a t i o n < 0 0 >
Ready by - requested energy must be diverted to the load by this time
(default: 00:00; format:hours:minutes).
Duration - minimum accumulated time the load must remain on (in
minutes; default: 00).
Schedule:
S e t < S c h e d u l e >
S t a r t T i m e < 0 0 : 0 0 >
E n d T i m e < 0 0 : 0 0 >
W e e k D a y s < 1 2 3 4 5 6 7 >
Smart Energy Socket
14 Configuration with Inverters with LCDScreen