Smart Save:
Ready by - requested energy must be diverted to the load by this time
(default: 00:00; format:hours:minutes).
Duration - minimum accumulated time the load must remain on (in
minutes; default: 00).
Schedule:
Start/End Time - the time of day by which the Smart Energy Hot Water must
start/ complete its task of delivering energy to the load (default: 00:00;
format:hours:minutes). If these values are not set, only the excess PV power
is used.
Week Days (optional) - days to repeat the settings (default: every day).
10. To use multiple schedules select Add Schedule and edit the settings.
11.
Select Device Properties and set the following properties:
Load Rating - the rated power (in kW) of the appliance
Min ONTime - (optional); the minimum duration (in minutes) the appliance
should remain ONonce switched on, even when no excess PVpower is
available. The default value is 5 minutes.
Export Threshold - optional; the minimum power (in W) above which the excess
PV power will be diverted to the appliance. This value can be lower than the
load rating. The default value is 5% above the Load Rating.
Import Threshold - optional; the maximum power (in W) purchased from the
grid and diverted to the appliance. The default value is 5% of the Load Rating.
NOTE
If changing the Export Threshold and Import Threshold default values,
make sure they sum up to a value that equals or greater than the
appliance Load Rating value. Otherwise, the device will turn off when
there is insufficient power to divert to the appliance.
Smart Energy Socket
18 Configuration with Inverters with SetApp