EasyManua.ls Logo

Solax X1-Hybrid Series - Advanced; Safety; Power Factor

Solax X1-Hybrid Series
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item
7
1
2
3
4
5
6
8
Country
VDE 0126
ARN 4015
German
AS 4777
Australia
EN 50549_EU
Netherland
EN 50438_NL
Netherland
CEI 0-21
Italy
IEC61727_In
India
Standard
German
G98/G99
UK
Mode Comment
Off
Under-Excited PF value
Over-Excited PF value
Curve
Upper limit
Lower limit
Power Upper
Power Lower
PFLockInPoint ( CEI 0-21 only)
PFLockOutPoint ( CEI 0-21 only)
Q( u )
QuVupRate
QuVlowRate
-
( EN50438_NL only)
( EN50438_NL only)
On-grid
(f-1)
Safety
Power Factor
Grid
Export Control
Self Test
(f-1-1)
(f-1-2)
(f-1-3)
(f-1-4)
(f-1-5)
(f-1-7)
DRM Function
P(U ) Function
(f-1-8)
(f-1-9)
(f-1-6)
GlblMPPTFunc
Remote Control
f-1-1) Safety
User can set safety standard according to different countries and grid tied
stanndards.There are 8 standards to select. (May change without notice)
f-1-2) Power Factor ( For specific country if required by the local grid.)
There are 5 modes for selecting: Off , Under-Excited, Over-Excited, Curve, Q( u ).
f ) Advanced
All the advance setting can be set here, such as battery, grid, EPS and so on.
Advanced” is divided four parts: On-grid, Battery, Reset, User-define. And every
part has lower level parts.
Pls contact with your installer or factory for the installer password to enter.
On-grid
Battery
Reset
Advanced
Reactive power control, Reactive standard curve cos φ = f(P)
For VDE ARN 4105, curve cos φ = f(P) should refer to curve A. default value of setting is as
shown in curve A.
For E 8001, curve cos φ = f(P) should refer to curve B. default value of setting is as shown in
curve B.
For CEI 0-21, default value of PFLockInPoint is 1.05, when Vac > 1.05Vn, and Pac> 0.2 Pn,
curve cos φ = f(P) should refer to curve C. Default value of PFLockOutPoint is 1 when Vac < 1
Vn, cos φ = f(P) will exit curve C.
59
58
Setting Setting
0.9/0.95*
0.9/0.95*
leading
p/p
lagging
curve A
0.5 1.0
over-excited
under-excited
0.2
1
Emax
cos φ