iQ Control Box
10.18.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 19
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Final Tune-In Adjustments
• Refer to ANSI/BHMA A156.10, “American Naonal Standard for Power Operated Pedestrian Doors,” or
ANSI/BHMA A156.19, “American Naonal Standard for Power Assist and Low Energy Power Operated Doors,”
or the most current ANSI/BHMA standards.
• CYCLE and RECYCLE door several mes to verify proper speeds and forces, and PERFORM adjustments in the
following order:
a. ADJUST CK (Close Check) cam.
b. ADJUST Open Speed.
c. ADJUST Open Check Speed.
d. ADJUST CLS (Close Speed) rheostat.
e. ADJUST CK (Close Check Speed) rheostat.
NOTE: Adjustments to the CK (Close Check) rheostat also aect closing speed.
Closing speed must always be checked aer adjusng Close Check Speed.
f. ADJUST CLS (Close Speed) rheostat.
Caution: To prevent motor overheang and premature motor failure, Stall Torque must not be
set too high.
g. ADJUST Stall Torque.
h. ADJUST torque.
i. ADJUST me delay.
Warning: The Magic-Touch™ Hold Open Time must be a minimum of 3 seconds to ensure compliance
with ANSI/BHMA A156.19 “American Naonal Standard for Power Assist and Low Energy Power
Operated Doors,” or most current ANSI/BHMA standards.
j. ADJUST Magic-Touch™ Hold Open Time.
k. ADJUST breakout and breakout status cams.
l. ADJUST Power Close Speeds, Torques and Angles.
m. ENSURE all ANSI/BHMA, and UL compliance requirements are met.
n. POWER DOWN the door, POWER UP the door, and ENSURE that all sengs have been stored
in the controller.
o. Verify that the correct Safety Logic has been selected for Sensor Monitoring and that JP301 is installed.
p. Please refer to Aachment 11 for iQ Controller Fine Tuning for adjustment recommendaons.