iQ Control Box
10.18.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 13
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Table 1. FIS Procedure Using Pushbuttons
Step Description
Display
Index Value
Status
Code
1 Set Funcon switch to Closed.
2 Turn power on.
3 Unlock keypad. 99 0 00
4 Restart FIS. 96 1 A0
5 Select door type (Refer to Table 2). 0 Refer to Table 2 A0
6 Select Motor 1 Handing. 1 00 = Right hand
01 = Le hand
A0
7 Select Motor 2 Handing. 2 00 = Right hand
01 = Le hand
A0
8 Accept FIS. Display will show A1. 3 1 A1
9 Make changes: Safety Logic.
(NOTE: If there are no sensors
connected, leave value of 00).
11 Safety Logic. INDEX 11 - 00 to 15
00 = Sensor
01 = Sentrex
02 = Carpet
03 = Carpet 12 Sec.
04 = Non-Monitored Bi-Fold
05 = Monitored DM & OHP. ACT, STL
& SAF, both single & pair
06 = Monitored DM & OHP Dual
Egress. STL, ACT, STL & SAF
07 = Monitored OHP & Photobeam.
SAF & Photobeam
08 = Monitored DM ACT. ACT both
single & pair
09 = Monitored OHP Bi-Fold. SAF
10 = Monitored DM. ACT & STL both
single & pair
11 = Two OHP Monitored Bi-fold. SAF,
Bi-Fold/Swing
12 = Monitored Hub Based Sensors.
ACT & STL
13 = Swing-Guard T
14 = Monitored DM Stall & OHP both
single and pair. STL & SAF
15 = Monitored DM Stall & OHP Dual
Egress. STL & SAF
A1
10 Lock Keypad. 99 01 00
11 Final Tune in. -- -- --
ABBREVIATIONS
DM Door Mounted Sensors
OHP Overhead Presence Sensor
ACT Acvaon Side Presence Sensor
STL Stall Presence Sensor
SAF Safety Presence Sensor
Index Tables