SUNFAR E300 SERIES 43
(5)Slave correspond
Slave data correspond to master is for action feedback of master order frame. It exists in all type
data frame shown as below:
Data Definition Data Definition
0
Slave receives data for normal
operation
1 Receive data beyond range
2
Slave running prohibit modifying
data
3
Data modification prohibited by
password
4
Try to read, reserve or hide
parameter
5 Reserved
6
Appointed parameter code or
invalid address
(beyond
limitation
)
7
When adopt ASC code
Ⅱ
transmission data, it exists invalid
ASC code character
Ⅱ
8
Invalid order type or operation
order
9~F
Reserved
When slave corresponding byte data is “6~8”, frame length of
corresponding frame is 11 byte.
Frame format is shown as below:
0 1 2 3 4 5 6 7 8 9
10
Slave
correspond
Slave addr.
Slave addr.
Slave
correspond
0 0
Check sum
Check sum
Check sum
Check sum
Tail
Definition
Header
Slave addr. Order/ corresponding area Check area 0DH