Page | 31
Max battery discharge current (Amps), which should be 20% of the Ah rating for AGM
only. For Lithium, please refer to the battery manufacturer documentation. Note: This
is a global max. discharge current for both ‘grid-tied’ and ‘backup’ modes of operation
and if the current exceeds this value inverter will shut down with an overload fault.
TEMPCO settings - Temperature coefficient is the error introduced by a change in
temperature.
What you can do from this page:
Use battery voltage for all settings (V).
Use battery SOC for all settings (%).
No battery: tick this box if no battery is connected to the system.
BMS setting.
Active battery - This feature will help recover a battery that is 100% discharged by slowly
changing from the solar array. Until the battery reaches a point where it can change
normally.
5.11. Generator and Battery Page
To configure battery charging settings, click on the BATTERY icon and then on ‘Batt
Charge’.
Float V for an AGM battery is 55.20V.
Absorption V is for an AGM battery is 57.60V.
Equalization V for an AGM battery is 58.80V.
Equalizing charge/overcharge to remove sulphate crystals that build-up on the plates
over time on lead-acid batteries.
What this page displays:
Generator start voltage/SOC %.
Grid power start voltage/SOC %.
Float V is the voltage at which a
battery is maintained after being
fully charged.
Absorption V the level of charge
that can be applied without
overheating the battery.