Function code Name Default Min. Unit Setting Range
F7-00 Testing oor 1 0 1 0~F6-00
F7-01 Testing oor 2 0 1 0~F6-00
F7-02 Testing oor 3 0 1 0~F6-00
F7-03 Testing oor 4 0 1 0~60000
It can set the target oor when the lift is in adjusting or service. Its setting range is from 0~F6-
00,but the commands of current oor and less than the oor F6-01 aren’t administered.
0:Testing oor is invalidation. Testing oor 1 is the sam
e with car call. Testing oor 2 is the
same with landing up call. Testing oor 3 is the same with landing down call. The command is
durative availability until code set to 0 instead.
NICE 3000 can run at random. There are 5s in each running interval when simulating the
daily running state. The times set by F7-03 are generated by the times of target oors occur at
random. If the setting time is ove
r 60000, the random running will keep on until the user sets
7-03 as 0.
F7-04
Landing call enable Default 0 Min. Unit 1
Setting Range 0、1
0:Landing call allowable;
1:Landing call forbidden
F7-05
Door open enable Default 0 Min. Unit 1
Setting Range 0、1
0:Door open allowable, door operator button useful;
1:Door open forbidden, door operator button unuseful and door don’t automatically open.
F7-06
Over load function selection Default 0 Min. Unit 1
Setting Range 0、1
0:Over load running forbidden;
1:Over load running allowable. When over load running is allowed, lift comes into over load
state, light of over load lights, and lift doesn’t respond to landing call, non-stop running to
target oor. Please set 0 when it’s in normal using.
F7-07
Limit enable Default 0 Min. Unit 1
Setting Range 0、1
0:End switch availability;
1:End switch invalidation. Only use it when checking limit switch.
:This F7 group functions are used by persons who possess professional
competency. Please pay more attention. The operator is in charge of the responsibilities.
Please make sure that the setting of the F7 group parameters is 0.