Function
Code
Name Setting Range Min. Unit Default
Modifi-
cation
FC-06
The first error
information
0~3199
Note: The first two figures mean the oor’s
number, and the last two mean the error code.
e.g. error 30 occurs in Floor1(the elevator’s
position is abnormal), the error information
displays 0130.
0: No error
1: Inverse unit protection
2: Over current accelerated
3: Over current decelerated
4: Over current cons
tant
5: Over voltage accelerated
6: Over voltage decelerated
7: Over voltage constant
8: Controller power fault
9: Under voltage fault
10:Controller overload
11: Motor overload
12: Input side phase loss
13: Output side phase loss
14: Module overheated
15: Reserved
16: Reserved
17:Contactor fault
18: Current detection fault
19: Motor tuning fault
20: Encoder fault
21: Synchronous motor encoder wiring error
22: Leve
ling inductor signal is abnormal
23: Short circuit fault to ground
24:Reserved
25: Data storage error
26~28: Reserved
29: Synchronous self-locking contactor
feedback is deviant
30: Lift position is deviant
31: DPRAM is deviant
32: CPU is deviant
33: Lift over speed error
34: Logic fault
35: shaft auto-tuning date is deviant
36: Contact feedback is deviant
37: Brake feedback is deviant
38: Controller encode sign
al is deviant
39: Motor overheated
40: Lift running condition is not satisfied
41: Safety circuit cut
42: Door lock cut when running
43: Upper limit signal cut when running
44: Lower limit signal cut when running
45: Up/Down force reducer switch cut
46: Re-leveling is deviant
47: Lock contactor is deviant
48: Door open fault
49: Door close fault
50: Group control communication fault
51: Inside call communicati
on fault
52: Outside call communication fault
53: Lock jump fault
1 0 ●
FC-07
The first error
month and day
0~1231 1 0 ●
FC-08
The second
error
information
0~3199 1 0 ●
FC-09
The second
error month and
day
0~1231 1 0 ●