EasyManua.ls Logo

Swann AMI CACE - Page 70

Swann AMI CACE
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68 A-96.250.871 / 120417
AMI CACE
Program List and Explanations
Examples of metering devices that are driven time proportional are
solenoid valves, peristaltic pumps.
Dosing is controlled by the operating time.
5.3.2.32.20 Cycle time: duration of one control cycle (on/off change).
Range: 0600 sec.
5.3.2.32.30 Response time: Minimal time the metering device needs to react.
Range: 0240 sec.
5.3.2.32.4 Control Parameters
Range for each Parameter same as 5.2.1.40, p. 60
Examples of metering devices that are pulse frequency driven are
the classic membrane pumps with a potential free triggering input.
Dosing is controlled by the repetition speed of dosing shots.
5.3.2.32.21 Pulse frequency: Max. pulses per minute the device is able to re-
spond to. Range: 20300/min.
5.3.2.32.31 Control Parameters
Range for each Parameter same as 5.2.1.40, p. 60
Dosing is controlled by the position of a motor driven mixing valve.
5.3.2.32.22 Run time: Time needed to open a completely closed valve
Range: 5300 Sec.
5.3.2.32.32 Neutral zone: Minimal response time in % of the runtime. If the re-
quested dosing output is smaller than the response time, no
change will take place.
Range: 120 %
5.3.2.32.4 Control Parameters
Range for each Parameter same as 5.2.1.40, p. 60
5.3.2.32.1 Actuator = Time proportional
5.3.2.32.1 Actuator = Frequency
5.3.2.32.1 Actuator = Motor valve

Table of Contents

Related product manuals