GB.COMPACTUT.170622
Registered design. The company reserves the right to make design changes without prior notice.
54 www.swegon.com
19 INFORMATIVE MESSAGES
Informative messages are displayed in the hand-held micro
terminal. Informative messages are displayed only when
the user is viewing the Main menu.
Informative messages provide particulars about neces-
sary settings that have not been entered or unfavourable
operating scenarios, for instance.
Message No.
Message Text
1
FILTER CALIBRATION NOT EXECUTED
The pressure across the filters was not calibrated after the first start. Recurrent at 24-hour intervals. The mes-
sage will not be received after the pressure across the filters has been calibrated.
2
H EXCH CALIBRATION NOT EXECUTED
The pressure across the heat exchanger was not calibrated after the function was activated for the first time.
Recurrent at 24-hour intervals. The message will not be received after the pressure across the heat exchanger
has been calibrated.
3
SPARE
4
INCORRECT DIP SWITCH SETTINGS
DIL switches on the control circuit card are set in a forbidden combination.
5
SPARE
6
E-MAIL ERROR
Error when e-mail is being delivered. The message will be displayed after ten attempts.
7
PREFILTER CAL NOT EXECUTED
The pressure across the prefilters was not calibrated after the first start. Recurrent at 24-hour intervals. The
message will not be received after the pressure across the prefilters has been calibrated.