Technician Menu Page 22/33
Programming instructions SYCLOPE ODISEA
®
b) Flocculant management
Allows management of flocculant injection in various modes.
For this function to be performed, it is necessary first to activate it in the configuration management
of the specialist level (see Chapter VII Paragraph 2: Flocculant).
In continuous mode :
Continuous flocculant injection
In timed mode
Program the flocculant injection ratio
In the example above, the controller will inject flocculant for 20 seconds and stop injecting for 40
seconds before resuming the cycle.
In flow meter mode
Set the number of pulses from the flow meter contact (to be connected to the
meter input WM) from which the central unit will inject the flocculant.
…….…...
..
…......…
General timers
Filtering
Flocculant
Printing
Storage rate
…….…...
.
..…..
....
Flocculant op.
Continuous
Timed
Flow meter
….…...
.
..…
. ..
.
..
Fct du floculant
Continu
Temporisé
bitmètre
…….….
...
..…
......…
Flocculant op.
Continuous
Timed
Flow meter
…….…
....
..…
......…
Flocculant op.
Continuous
Timed
Flow meter
Ratio…(sec/min): 020
…….…...
.
..….
.....…
Flocculant op.
Continuous
Timed
Flow meter
…….….
...
..
......…
Flocculant op.
Continuous
Timed
Flow meter
No. of pulses : 050