Gas airtight suspended warm air heaters - EOLO
11
SYSTEMA S.p.A.
Rev. 10EE0112
d) Fan-limit safety bi-thermostat with automatic reset: this has a double aim:
-to control start-up of the fans after the air has reached 50°C and shut-down of these when the air
temperature has dropped below 30°C;
-to interrupt operation of the appliance if there is abnormal overheating of the air (>90°C); the appliance
can be reset manually using the reset button located on the board.
SAFETY BI-THERMOSTAT TECHNICAL SPECIFICATIONS
Limit control ........................................................................................... 4 (4) A
Fan control ............................................................................................ 7 (7) A
Supply voltage ....................................................................................... 230-240 V