EasyManua.ls Logo

TDK-Lambda GENESYS 1500W - Service Request: Enable and Event Registers

TDK-Lambda GENESYS 1500W
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
83
-
507
-
013 Rev. D
65
Refer to Tables 7
-
10 to 7
-
13 for details of the Enable and Event registers.
1.
Fault Enable Register
The Fault Enable Register is set to the enable faults SRQs.
Table 7
-
10: Fault Enable Register
BIT
Enable
bit name
Fault symbol
Bit Set condi
tion
Bit reset condition
0 (LSB)
Spare bit
SPARE
1
AC Fail
AC
2
Over Temperature
OTP
3
Foldback
FOLD
4
Over Voltage
OVP
5
Shut Off
SO
6
Output Off
OFF
7(MSB)
Enable
ENA
User command:
“FENA nn” where
nn is hexadecimal
User command: “FENA nn”
where nn is hexadecimal (if
nn=”00”, no fault SRQs will
be generated).
2.
Fault Event Register
The Fault Event will set a bit if a condition occurs and it is Enabled. The register is cleared when
FEVE?, CLS or RST commands are received.
Table 7
-
11: Fault Event Register
BIT
Enable
bit name
Fault symbol
Bit Set condition
Bit reset condition
0 (LSB)
Spare bit
SPARE
1
AC Fail
AC
2
Over Temperature
OTP
3
Foldback
FOLD
4
Over Voltage
OV
P
5
Shut Off
SO
6
Output Off
OFF
7(MSB)
Enable
ENA
Fault condition
occurs and it is
e
n
abled.
The fault can set a
bit, but when the
fault clears the bit
remains set.
Entire Event Re
gister is
cleared when user sends
“FEVE?” command to read
the register.
“CLS” and power
-
up also
clear the Fault Event Regi
s-
ter. (The Fault Event Regi
s-
ter is not cleared by RST)

Table of Contents