EasyManua.ls Logo

TECNA TE 500 - First Insertion Delay Adjustment

TECNA TE 500
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51 / 52
FIRST INSERTION DELAY ADJUSTMENT
During the installation phase, the first insertion delay is to be adjusted. This adjustment allows the
optimizing of the welder's line consumption balance. Adjust by setting the control unit to maximum
power (CURRENT 1 = 99%) and carry out "loadless" welding spots, interrupting the secondary circuit
(e.g. by placing non-conducting material in between the electrodes). Adjust the "FIRST DELAY"
parameter (see the "INSTALLATION" paragraph) so that positive and negative line consumptions are
balanced. It is possible to use two different solutions for measuring the primary current:
Use an ammeter capable of measuring positive and negative maximum peak values (such as the
TECNA TE1600). In this manner the adjustment will be correct when the positive peak value will be
similar to the negative one. The value of the current consumed by the welder (when loadless) might be
too low for the instrument's minimum capacity. Solve this problem by running the cable, on which the
measurement is being taken, inside the current sensor several times. In this case the read value will be
multiplied by the same number of cable-run-through operations performed in the sensor.
Use an ammeter that allows the displaying of the wave forms on a digital oscilloscope. In this case
perform the adjustment so that all the half waves of the primary current have the same amplitude. The
graphs below show the wave forms achieved both with an incorrect and a correct adjustment.
Unbalanced consumption Balanced consumption