8 / 52
There are few special conditions:
• If OFF TIME is set to (0), the welding control unit will work in single cycle.
• If OFF TIME is set to (99), the welding control unit will carry out the min. current compensation with a
value lower than 2.0 kA (see paragraph "COMPENSATION OF THE SECONDARY CURRENT")
• By setting the PRE-WELD parameter to zero, the pre-weld is not carried out.
• By setting the POST-WELD parameter to zero, the post-weld is not carried out.
PARAMETER DESCRIPTION VALUE RANGE
WORK MODE WORK MODE IK - PW%-FIX
CONTROL MODE CONTROL MODE NO - CURR - DEG
1 SQUEEZE 1 1s1 SQUEEZE TIME 01 - 99 cycles
2 SQUEEZE SQUEEZE TIME 00 - 99 cycles
3 PRESSURE WELDING PRESSURE 00 - 99 cycles
4 FORGE DELAY FORGING TIME 00 - 99 cycles
5 PRE-WELD PRE-WELD TIME 00.0 - 99.5 cycles
6 PRE-POWER PRE-WELD CURRENT 05 - 99%
7 COLD I COLD 1 TIME 00 - 50 cycles
8 SLOPE UP SLOPE UP TIME 00 - 25 cycles
9 WELD 1 WELDING TIME 00.5 - 99.5 cycles
10
POWER 1
CURRENT 1
WELDING CURRENT
5 - 99%
1.0 - 90.0 kA
11 COLD 2 COLD 2 TIME 01 - 50 cycles
12 N. IMPULSE NUMBER OF IMPULSES 00 - 09
13 SLOPE DOWN SLOPE DOWN TIME 00 - 25 cycles
14 COLD 3 COLD 3 TIME 00 - 50 cycles
15 POST-WELD POST-WELD TIME 00.0 - 99.5 cycles
16 POST-POWER POST-WELD CURRENT 05 - 99%
17 HOLD TIME HOLD TIME 01 - 99 cycles
18 OFF TIME DWELL TIME 00 - 99 cycles
19 CURR MIN MIN LIMIT IN CURRENT 1.0 - 90.0 kA
20 CURR MAX. MAX. LIMIT IN CURRENT 1.0 - 90.0 kA
21 ANGLE MIN MIN LIMIT IN DEGREES 001° - 180°
22 ANGLE MAX. MAX. LIMIT IN DEGREES 001° - 180°
WORK PROGRAM PARAMETERS TABLE
If CONTROL MODE is activated it will be possible to have additional parameters, namely:
if the CONTROL MODE parameter is set to CURR, otherwise
if the parameter is set to DEG.