4-70
11-Performance Control Parameters
11-00
Prevention of Reverse operation
Range
0: Reverse command is enabled
1: Reverse command is disabled
11-00=1: he reverse command is disabled.
11-01
Carrier Frequency
Range
1~16KHz
11-02
Carrier mode selection
Range
0: Carrier mode0 3-phase PWM modulation
1: Carrier mode1 2-phase PWM modulation
2: Carrier mode2 2-phase soft PWM modulation
Mode 0: 3-phase PWM Modulation Three output transistors on at the same time (Full Duty).
Mode 1: 2-phase PWM Modulation Two output transistors on at the same time (2/3 Duty).
Mode 2: Soft PWM Modulation: 3-phase PWM and 2-phase PWM modulation used randomly.
Note: Mode 2 can improve life of the IGBTs, control temperature rise and suppress electromagnetic noise.
Modes
Name
IGBT Duty
Heat
Losses
Torque
Performance
Waveform
Distortion
Motor Noise
0
3-Phase PWM
100%
High
High
Low
Low
1
2-Phase PWM
66.6%
Low
Low
High
High
2
Soft PWM
66.6%
Low
Low
High
High
11-03
Carrier Frequency auto reduction due to temperature rise
Range
0:Disable
1:Enable
When inverter (heatsink) temperature rises above 176°F/80°C the Carrier Frequency is automatically
reduced to 4 kHz.
When the temperature falls below 158°F/70°C, Carrier Frequency is reset back to its original setting.
Temperature can be displayed by setting parameter 12-00=04000.
158ºF/70ºC
176ºF/80ºC
t1
t2
T0