11-Performance Control Parameters
Prevention of Reverse operation
【0】: Reverse command is enabled
【1】: Reverse command is disabled
11-00=1: he reverse command is disabled.
【0】: Carrier mode0 3-phase PWM modulation
【1】: Carrier mode1 2-phase PWM modulation
【2】: Carrier mode2 2-phase soft PWM modulation
Mode 0: 3-phase PWM Modulation Three output transistors on at the same time (Full Duty).
Mode 1: 2-phase PWM Modulation Two output transistors on at the same time (2/3 Duty).
Mode 2: Soft PWM Modulation: 3-phase PWM and 2-phase PWM modulation used randomly.
Note: Mode 2 can improve life of the IGBTs, control temperature rise and suppress electromagnetic noise.
Carrier Frequency auto reduction due to temperature rise
When inverter (heatsink) temperature rises above 176°F/80°C the Carrier Frequency is automatically
reduced to 4 kHz.
When the temperature falls below 158°F/70°C, Carrier Frequency is reset back to its original setting.
Temperature can be displayed by setting parameter 12-00=04000.
158ºF/70ºC
176ºF/80ºC
t1
t2
T0
Temperature
Carrier
Frequency
10KHz
4KHz
t1
t2
T0