7-1
7. Operation Method Configuration (Run / Stop)
The inverter offers users several choices to run and stop from different sources. The most commonly used
methods are described in the next sections.
Operation command is selected with parameter 00-02.
00-02: Run Command Selection
This function sets the frequency command source.
Setting Range: 0 to 2
To set parameter 00-02:
- After power-up press the MODE key
- Select 00-02 using the arrow keys and up/down keys
- Press </ENTER key
- Set parameter 00-02 using the arrow keys and </ENTER key to save setting.
In the parameter list move cursor to 00-01 with the UP/DOWN keys and press READ/ ENTER key to select.
00-02
Run Command Selection
Range
0: Keypad control
1: External terminal control
2: Communication control
7.1 Run/Stop from the Keypad (00-02=0) Default Setting
Use the RUN key to run the drive in forward direction.
Press STOP key to stop the inverter. (Note: Stop method can be set with
parameter 07-09, default is deceleration to stop).