6-5
Examples:
Frequency Reference Command: 10.00 Hz (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 02 03 E8 23 B8
To set the frequency reference to 10.00, a value of ‘1000’ (03E8h) has to be send to the inverter.
Frequency Reference Command: 30.00 Hz (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 02 0B B8 24 44
To set the frequency reference to 30.00, a value of ‘3000’ (0BB8h) has to be send to the inverter.
Frequency Reference Command: 60.00 Hz (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 02 17 70 2D 12
To set the frequency reference to 60.00, a value of ‘6000’ (1770h) has to be send to the inverter
Note: The last 2 bytes of the command strings consist of a CRC16 checksum.
6.4 Change Output Frequency Unit from Hz to rpm
Enter motor base rpm into parameter 12-03 to change the display units from Hz to rpm.
12-03
Custom Units (Line Speed) Value
Range
0 - 65535