6-5 
Examples:   
 
Frequency Reference Command: 10.00 Hz (Inverter Node Address: 01) 
 
Command String (hexadecimal): 01 06 25 02 03 E8 23 B8 
 
To set the frequency reference to 10.00, a value of ‘1000’ (03E8h) has to be send to the inverter.   
 
Frequency Reference Command: 30.00 Hz (Inverter Node Address: 01) 
 
Command String (hexadecimal): 01 06 25 02 0B B8 24 44 
 
To set the frequency reference to 30.00, a value of ‘3000’ (0BB8h) has to be send to the inverter. 
 
Frequency Reference Command: 60.00 Hz (Inverter Node Address: 01) 
 
Command String (hexadecimal): 01 06 25 02 17 70 2D 12 
 
To set the frequency reference to 60.00, a value of ‘6000’ (1770h) has to be send to the inverter 
 
Note: The last 2 bytes of the command strings consist of a CRC16 checksum. 
 
6.4 Change Output Frequency Unit from Hz to rpm 
 
Enter motor base rpm into parameter 12-03 to change the display units from Hz to rpm. 
 
Custom Units (Line Speed) Value