TECO L510 - Analog Output Setup

TECO L510
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-6
8.6 Analog Output Setup
Signal: Use parameter 04-11 to select the analog output signal for AO.
Gain: Use parameter 04-12 to adjust the gain for AO. Adjust the gain so that the analog output (10V) matches
100% of the selected analog output signal (04-11 for AO).
Bias: Use parameter 04-13 to adjust the bias for AO. Adjust the bias so that the analog output (0V) matches 0%
of the selected analog output signal (04-11 for AO).
Example: Analog Output AO Wiring
RA
RB
COM /
+12V
S1
S2
S3 S4
S5
10V
AGND
AVI
ACI
AO
Control Terminals /
User Terminals
Connect shield
to control
ground terminal
Common/
AGND
Analog
Output AO
+
-
04-11
AO function Setting
Range
0: Output frequency
1: Frequency command
2: Output voltage
3: DC voltage
4: Motor current
04-12
AO Gain
Range
0 ~ 1000%
04-13
AO Bias
Range
0 ~ 100%
04-14
AO Bias Selection
Range
0: Positive 1: Negative
04-15
AO Slope
Range
0: Positive 1: Negative