8-6
8.6 Analog Output Setup
Signal: Use parameter 04-11 to select the analog output signal for AO.
Gain: Use parameter 04-12 to adjust the gain for AO. Adjust the gain so that the analog output (10V) matches
100% of the selected analog output signal (04-11 for AO).
Bias: Use parameter 04-13 to adjust the bias for AO. Adjust the bias so that the analog output (0V) matches 0%
of the selected analog output signal (04-11 for AO).
Example: Analog Output AO Wiring
RA
RB
COM /
+12V
S1
S2
S3 S4
S5
10V
AGND
AVI
ACI
AO
Control Terminals /
User Terminals
Connect shield
to control
ground terminal
Common/
AGND
Analog
Output AO
+
-
0: Output frequency
1: Frequency command
2: Output voltage
3: DC voltage
4: Motor current
【0】: Positive 【1】: Negative
【0】: Positive 【1】: Negative