6-1
6. Speed Reference Command Configuration
The inverter offers users several choices to set the speed reference source. The most commonly used methods
are described in the next sections.
Frequency reference command is selected with parameter 00-05.
00-05: Main Frequency Source Selection (Frequency Source)
This function sets the frequency command source.
Setting Range: 0 to 6
To set parameter 00-05:
- After power-up press the MODE key
- Select 00-05 using the arrow keys and up/down keys
- Press </ENTER key
- Set parameter 00-05 using the arrow keys and </ENTER key to save setting.
Main Frequency Command Source Selection
0: Keypad
1: Potentiometer on Keypad
2: External AVI Analog Signal Input
3: External ACI Analog Signal Input
4: External Up/Down Freq. Control
5: Communication Setting Freq.
6: PID Output Freq.
6.1 Reference from Keypad
Speed reference from the keypad is the default setting. Press▲ and ▼ keys to change the speed reference.