EasyManua.ls Logo

TECO L510 - AC Line Reactors

TECO L510
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-2
11.2 AC Line Reactors
An AC line reactor can be used for any of the following:
- Capacity of power system is much larger than the inverter rating.
- Inverter mounted close to the power system (in 33ft / 10 meters).
- Reduce harmonic contribution (improve power factor) back to the power line.
- Protect inverter input diode front-end by reducing short-circuit current.
- Minimize overvoltage trips due to voltage transients.
Please select the AC line reactor based on the inverter rating according to the following table.
Table 11.2 List of AC Line Reactors (3%) - Chassis
Model
AC reactor
Input
Voltage
HP
Rated Current(A)
HD/ND
Part Number
230V
1Ø/3Ø
0.25
4.6
KDRULA25L
0.5
4.6
KDRULA25L
1
4.6
KDRULA25L
1.5
6.6
KDRULA26L
2
7.5
KDRULA27L
3
10.6
KDRULA28L
Model
AC reactor
Input
Voltage
HP
Rated Current(A)
HD/ND
Part Number
460V
1
2.1
KDRULA8L
2
3.4
KDRULA1L
3
4.8
KDRULA2L
Contact TWMC for any assistance
Note: AC reactors listed in this table can only be used for the inverter input side. Do not connect AC reactor to the inverter output side.