8-4
8.4 Rapid Stop / Decel to Stop
To use the rapid stop function set any of the multi-function digital input function to #14 (Rapid stop). When rapid
stop input is activated the inverter will decelerate to a stop and display the [ES] condition on the keypad.
Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Example: Rapid Stop Switch set for input terminal S5 (03-04 = 14).
RA
RB
COM /
+12V
S1
S2
S3 S4
S5
10V
AGND
AVI
ACI
AO
Rapid Stop Switch
(Maintained)
Connect
shield to
control
ground
terminal
Rapid Stop
Common/
+12V
Control Terminals /
User Terminals