3-10
3.8 User Terminals (Control Circuit Terminals)
Terminal symbols
TM1 Function Description
RA
Relay output terminal, Specification: 250VAC/1A(30VDC/1A)
RB
COM
S1~S5 (COMMON) NPN
S1
Multi-function input terminals(refer to group3)
S2
S3
S4
S5
10V
Built in Power for an external speed potentiometer
AVI
Analog voltage input, Specification : 0~10VDC/ 2-10V
ACI
Analog current input, Specification : 0/4~20mA
AO
Multi-function analog output terminal. Maximum output 10VDC/1mA
AGND
Analog ground terminal
NPN:
Notes:
*1:Multi-function digital input can be referred to in this manual.
- Group 03: External Terminals Digital Input / Output Function Group.
*2:Multi-function analog input can be referred to in this manual..
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
*3:Multi-function analog output can be referred to in this manual.
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
Caution
Maximum output current capacity for terminal 12V is 20mA.
Multi-function analog output AO is used for an analog output meter. Do not use these output for
feedback control.
Control board’s 12V/24V are to be used for internal control only, Do not use the internal
power-supply to power external devices.
RA RB COM S1 S2 S3 S4 S5 10V AVI ACI AO AGND