7-3
Momentary Contacts (Push Buttons)
Use push button / momentary switch to Run and Stop the inverter.
Set parameter 00-04 to 2 for 3-wire program initialization, multi-function input terminal S1 is set to run operation,
S2 for stop operation and S3 for forward/reverse command.
00-01 Operation Method = 1
00-04 Operation modes for external terminals = 2
RA RB
COM /
+12V
S1 S2 S3 S4 S5 10V AGNDAVI ACI AO
Connect
shield
to
control
ground
terminal
START
PUSH BUTTON
(Momentary)
STOP
PUSH BUTTON
(Momentary)
Reverse direction
when closed
Note: Stop mode selection can be set with parameter 07-09, default is deceleration to stop.