10-2 
 
DC bus voltage is 
lower than the UV 
detection level or 
the pre-charge 
contactor is not 
active while the 
inverter is running. 
190Vdc: 230V 
class;   
380Vdc: 460V   
class; 
The detection value 
can be adjusted by 
07-13). 
  The input voltage is too low. 
  Input phase loss. 
  Acceleration time set too short.   
  Input voltage fluctuation.   
  Pre-charge contactor damaged. 
  DC bus voltage feedback signal value not 
incorrect. 
  Check the input voltage. 
  Check input wiring. 
  Increase acceleration time. 
  Check power source 
  Replace pre-charge contactor 
  Replace control board or 
complete inverter. 
The temperature of 
the heat sink is too 
high. 
Note: when OH 
fault occurs three 
times within five 
minutes, it is 
required to wait 10 
minutes before 
resetting the fault. 
  Ambient temperature too high. 
  cooling fan failed 
  Carrier frequency set too high. 
  Load too heavy. 
  Install fan or AC to cool 
surroundings. 
  Replace cooling fan. 
  Reduce carrier frequency. 
  Reduce load / Measure output 
current 
The temperature of 
the heat sink is too 
high. 
Note: when OH 
fault occurs three 
times within five 
minutes, it is 
required to wait 10 
minutes before 
resetting the fault. 
  Ambient temperature too high. 
  cooling fan failed 
  Carrier frequency set too high. 
  Load too heavy. 
  Install fan or AC to cool 
surroundings. 
  Replace cooling fan. 
  Reduce carrier frequency. 
  Reduce load / Measure output 
current 
  Abnormal input voltage, too much noise or 
malfunctioning control board. 
  Check input voltage signal and 
the voltage on the control 
board. 
Inverter capacity 
setting error: 
Inverter capacity 
13-00 does not 
match the rated 
voltage 
  The inverter capacity setting (13-00) does 
not match the hardware voltage levels 
  Check inverter capacity setting 
(13-00) to meet the hardware 
voltage levels. 
  External noise interference 
  Remove interference source 
then restart drive by switching 
power OFF/ON. 
  If not resolved contact supplier. 
OC-A   
over current at 
acceleration 
The inverter output 
current exceeds the 
  Acceleration / Deceleration time is too short.   
  Contactor at the inverter output side.   
  A special motor or applicable capacity is 
  Extend acceleration / 
deceleration time. 
  Check the motor wiring.