4-30
Set motor parameters 02-01 and 02-03~02-06,next set 02-07 to【1】to start the auto tune procedure.
During the Auto tune the display will show AT and show END briefly when auto tune is completed then the
display will return back to show frequency.
After a successful auto tune the motor test data is stored in parameters 02-08 and 02-09 and parameter 02-07 is
set back to 0.
Notes:
Perform an auto tune whenever the motor is replaced.
Auto tuning is not possible for applications with multiple motors connected to one inverter.
Auto tune can be used on motors of similar size to the inverter or one size smaller. Make sure to set the correct
motor parameters.
Parameters 02-00 ~ 02-06 are available both for V/F & SLV mode (Except parameter 02-02 V/f only).
SLV Slip Compensation Gain
SLV Torque Compensation Gain
SLV Slip compensation
When the load causes the actual motor speed to fall below the set speed due to the slip of the motor,
parameter 02-13 (SLV only) can be used to compensate and correct the speed.
SLV Torque compensation
When torque is reduced due to load conditions, parameter 02-14 can be used to correct the torque producing
current and compensate for the reduced torque.
Both 02-13 and 02-14 compensation are based on the load current. Parameter 02-13 is based on rated slip
frequency and 02-14 is based on the difference in rated torque.
Adjust 02-14 in steps of 5 to 10% up or down if needed.
Low Frequency Torque Gain
When operating at low output frequency (IGBT dead zone) results in a lower output torque of the
system and therefor resulting in lower motor efficiency. Setting 02-15 can increase output torque at low
frequency. Default setting is 50% voltage compensation. 100% of 02-15 is based on the output voltage of
the dead zone.