4-36
See example in the following diagram.
Accel/Decel & Enable/Disable timing diagram using terminal S1 and parameter 03-00 = 11.
RUN Command
S1
RUN
STOP
ON
OFF
ON
OFF
T
Hz
7) 03-00~03-04 =【12】Main/ Alternative run source select.
When any of the input terminal is set to function【12】and is turned on, the run command source is based on
parameter 00-03 (Alternative Run source).If the Input is off run command source will revert back to the setting in
parameter 00-02 (Main run source).
8) 03-00~03-04 =【13】Main/ Alternative Frequency source Select
When any of the input terminal is set to function【13】and is turned on, the frequency source is set based on
parameter 00-06 (Alternative Frequency source If the Input is off frequency source will revert back to the setting in
parameter 00-05 (Main Frequency source).
9) 03-00~03-04=【14】Rapid Stop (controlled deceleration stop)
When any of the input terminal is set to function【14】and is turned on, the inverter decelerates to a stop.
10) 03-00~03-04=【15】Base Block (Coast to stop)
When any of the input terminal is set to function【15】and is turned on, the inverter output is turned off.
11) 03-00~03-04=【16】Disable PID Function.
When any of the input terminal is set to function【16】and is turned on, the PID function is disabled. If the input is
turned off, PID function is enabled again.
12) 03-00~03-04=【17】Reset
When any of the input terminal is set to function【17】and is turned on, the existing fault is reset when no run
command is present. (Same function as the Reset button on keypad).
13) 03-00~03-04=【18】Auto _ Run Mode
When any of the input terminal is set to function【18】and is turned on, the programmable auto- sequencer function
is enabled, Refer to description in parameter group 6.