4-61
Operation After Overload Protection is Activated
【0】:Coast-to-Stop in case of a motor overload condition
【1】:Drive Will Not Trip in case of a motor overload condition (OL1)
08-06 = 【0】: In case of a motor overload condition the inverter will coast to stop and the display will flash
OL1. To reset Press the ‘Reset’ key or use an external reset clear the fault and continue to run.
08-06 = 【1】: On overload condition the inverter continues to run, display flash with OL1, until the current falls
below the overload level.
Minutes
1.0
150
Output Current (%)
5.0
103
【0】:Auto (Depends on heatsink temp.)
【1】:Active while inverter is running
【2】:Always Run
【3】:Disabled
08-07=【0】: Cooling fan runs as the inverter detects temperature rise.
08-07=【1】: Cooling fan runs while the inverter is running.
08-07=【2】: Cooling fan runs continuously.
08-07=【3】: Cooling fan is disabled.
【0】:AVR function enabled
【1】:AVR function disabled
【2】:AVR function disabled for stop
【3】:AVR function disable for Deceleration
【4】:AVR function disabled for stop & Deceleration from one speed to another speed.
【5】:when VDC>(360V/740V), AVR function is disabled for stop and
Deceleration
08-08=0. AVR enabled stabilizes the motor voltage independent of fluctuation to the input voltage.
08-08=1. Input voltage fluctuations will cause fluctuations on output voltage.
08-08=2. AVR is disabled during stopping to avoid an increase in stopping time.
08-08=3. AVR is disabled only during deceleration from one speed to another speed to avoid a longer
deceleration time.
Input phase loss protection
When 08-09=【1】: Phase loss warring message PF is displayed when an input phase loss is detected.