N3 Drive Operations Manual 
 
Routine Periodic Inspection     97 
 
23.0 Routine periodic inspection 
To ensure safe and secure operations, check and maintain the inverter and motor at regular intervals, the table below 
lists the suggested items to be checked on a periodic basis. 
 
 
 
 
 
 
Ambient 
conditions 
around the 
drive 
Confirm that the 
temperature and 
humidity is within 
specification 
Measure with 
thermometer 
and hygrometer 
Temperature: 
 -10 – 40
o
C 
  (14-120℉) 
 Humidity:  
Below 95% RH 
Improve the 
ambient or 
relocate the 
drive. 
Are there 
flammable or 
corrosive materials 
in the vicinity? 
Installation and 
grounding of 
the inverter 
Any excessive vibration 
from the machine ? 
Is the ground 
bonding resistance 
correct? 
Measure the 
resistance 
with a multi-
tester 
200V series: below 
100Ω 
400V series: below 
10Ω 
Measure the 
voltage with a 
multi-tester 
Voltage must 
conform with the 
specifications 
External 
terminals and 
internal 
mounting 
screws of the 
inverter 
Visually check & 
Check with a 
screwdriver 
Secure terminals 
and no rust present 
Secure or return 
for repair 
Is the terminal base 
damaged? 
Visual rust stains 
present? 
Internal wiring 
of the inverter 
Any unusual bends or 
breaks? 
Replace or return 
for repair 
Any damage of the 
wire insulation? 
Printed circuit 
boards & 
power 
modules 
Excessive dust or 
debris. 
Clean surfaces with 
no discoloration. 
Clean or replace 
the  circuit board 
or power 
modules 
Discolored, 
overheated, or 
burned parts 
Unusual vibration 
and/or noise 
Any unusual odor or 
leakage 
Replace 
capacitor  or 
inverter 
To prevent injury to personnel and damage to the equipment, wait 5 minutes after 
the “charge indicator” extinguishes before touching any parts.