7.0 Power Terminals Designations and Ratings (Terminal Block TM1) 
 
Depending on inverter ratings, the power terminals (TM1) can have one of three configurations. These are shown as 
A), B), C) and D) in Fig. 7.1. Section 7.2 covers the electrical ratings and tightening torques of the terminals.  
 
  Do Not over tighten terminal screws. (See Sec. 7.2) 
 
  Use the proper wire size for terminal connections. 
 
  Use proper termination techniques. 
 
7.1 Power Terminal Configuration TM1 
 
 
   
R/L1 S/L2 T/L3
B1/P
_
B2
UT1 VT2
WT3
Power Dynamic To Motor
230V 3Ø: 15 – 20 HP
460V 3Ø: 20 HP
R/L1 S/L2
T/L3
_
UT1
VT2
WT3
+
230V 3Ø : 25 - 40 HP
460V 3Ø : 25 - 75 HP
 Fig.7.1 Power Terminal Configuration TM1
     Terminal                     Connections
R/L1 – S/L2 – T/L3
U/T1 – V/T2 – W/T3
B1/P – B2
B1/P –
_
     Terminal                     Connections
 – 
_
+
External DC Supply
Or External Braking 
Unit.
                          230V 3Ø: 0.5 – 2 HP
                          460V 3Ø: 1 – 2 HP
230V 1Ø: 0.5 – 1 HP 
 Terminal                Connections
(L) – (N)
L1 – L2 – L3
T1 – T2 – T3
P1 – BR
P1 – P *
PE
A)
C)
D)
TM1
TM1
TM1
Do Not remove the 
Factory  Installed 
Jumper between 
Terminals P – P1 
unless a DC reactor 
is being installed.
 CAUTION
230V 3Ø: 0.5 – 2 HP
460V 3Ø: 1 – 2 HP
230V 1Ø: 0.5 – 1 HP 
3Ø Motor Output 
Braking Resistor Connection
DC Reactor Connections
Earth Ground
3Ø Input Power
3Ø Motor Output 
Braking Resistor
External DC Supply
R/L1 – S/L2 – T/L3
U/T1 – V/T2 – W/T3
3Ø Input Power
3Ø Motor Output 
L1(L)
L2
L3(N)
T1
T2
T3
PEPE
BRP
P1
(L) – (N)
L1 – L2 – L3
T1 – T2 – T3
P1 – BR
P1 – P *
230V 3Ø: 3 – 10 HP
460V 3Ø: 3 – 15 HP
230V 1Ø: 2 – 3 HP 
3Ø Motor Output 
Braking Resistor Connection
DC Reactor Connections
 Terminal                Connections
L1 L2 L3(N)
P1
BR
T1 T2
T3
Power Dynamic To Motor
P
TM1
                          230V 3Ø: 3 – 10 HP
                          460V 3Ø: 3 – 15 HP
230V 1Ø: 2 – 3 HP 
B)
Do Not remove the Factory  Installed Jumper between 
Terminals P – P1 unless a DC reactor is being installed.
 CAUTION