TECO N3 Series - Fig. 22.4 Motor will Not Run

TECO N3 Series
115 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N3 Drive Operations Manual
Troubleshooting Flow Chart; Motor Will Not Run 95
is MCCB
On ?
is MCCB
tripped ?
Wiring short circuit
No
Yes
Are voltages
Between power terminals
correct ?
Is the charge indicator
LED on ?
Input voltage or wiring is
incorrect
No
N3 fault
No
Is the the run command
on ?
No
Turn on the run command
Is there output voltage
to the U,V, and W
terminals ?
N3 fault
No
Are the output
voltages between
U,V, and W terminals
the same?
No
N3 fault
Motor faulty or wiring
is bad
Motor will not run
Yes
Yes
Yes
Yes
Yes (Note 2)
NOTES:
1 - The voltage between input terminals should be within 10%
of the nominal value.
2 - The voltage deviation should be within ± 3% of the value
without the motor.
Yes (Note 1)
Fig. 22.4 Motor Will Not Run