N3 Drive Operations Manual
Appendix A- General Specifications Cont. A2
1. RS232 or RS485
2. Multiple inverter networking (RS485 ONLY).
3. Baud rate, stop bit and parity can be set.
20% - 100% for models with built-in braking transistor and braking resistor.
14-120°F (-10 - 50°C) (Note3)
- 4 to 140°F (-20 to 60°C)
0 – 95% Relative humidity (Non-condensing)
< 3,281 ft. (1000m) (De-rate for higher altitudes)
Complies with requirement EN 61800-3 (with optional filter).
Complies with requirement EN 50178
IP20 ( NEMA with external enclosure)
230V class: DC voltage>410V 460V class: DC voltage>820V
230V class: DC voltage<190V 460V class: DC voltage<380V
Momentary power loss
restart
For power interruptions of 15 ms or more and less than 2 sec., operation can be
continued. (refer to parameters A013 & A014)
Stall prevention for acceleration/ deceleration/ operation.
Short-circuit output terminal
Electronic circuit protection
Electronic circuit protection
Protection for overheating of heat sink, over torque detection, error contact control,
reverse prohibit, prohibit for direct start after power up, and error recovery, and
parameter lock out.
Note 1: 220V, 15HP and above are not CE compliant
Note 2: The frequency setting resolution above 100Hz is 0.1Hz when controlled by the keypad and 0.01 Hz when
controlled by a computer (PC) or programmable controller (PLC).
Note 3: 14 -120°F (–10 - 50°C) Open chassis (without dustproof cover),
14 -104°F (–10 - 40°C) NEMA 1 (with dustproof cover).