EasyManua.ls Logo

TECO N3 Series - Page 114

TECO N3 Series
115 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N3 Drive Operations Manual
Appendix G Version 1.3 Changes Cont. G2
VER.
Parameter
LCD Display
Description
Range
Factory
Setting
1.3
A097
AI2 Gain
AI2 Gain (%)
AI2
0 - 200
100
Prior
A097
AI2 Gain
AI2 Gain (%)
S6
0 - 200
100
VER.
Parameter
LCD Display
Description
Range
Factory
Setting
1.3
A154
AIN AI2 Source
AIN or AI2
Source
Signal
0000: AIN = 0 -10V or 0 - 20mA
AI2 = 0 -10V or 0 - 20mA
0001: AIN = 0 -10V or 0 - 20mA
AI2 = 2 -10V or 4 - 20 mA
0002: AIN = 2 -10V or 4 - 20 mA
AI2 = 0 -10V or 0 - 20mA
0003: AIN = 2 -10V or 4 - 20 mA
AI2 = 2 -10V or 4 - 20 mA
0000
Prior
A154
PID Comm.
Source
PID
Feedback
signal
0000: 0-10V or 0-20mA
0001: 2-10V or 4-20mA
0000
Parameters A161 and A162 were added and selections 0025 and 0026 were added for parameters A050 A055.
VER.
Parameter
LCD Display
Description
Range
Factory
Setting
1.3
A161
Comm Error
Operation Sel
Communica-
tions
time-out
operation
selection
0000: Deceleration to stop.
(b008: Deceleration time 1)
0001: Coast to stop.
0002: Deceleration to stop.
(A026: Deceleration time 2)
0003: Continue operating.
0000
A162
Comm Error
detection time.
Communica-
tions
time-out
detection
time.
00.0 - 25.5 Sec.
00.00
A050-A056
S1 S6
Term Sel
Multifunctional
Input Term.
S1 S6
0025: Emergency Stop B Contact
See
Sec.
19.0
0026: Base Block B Contact
Important Throughout this manual, multifunctional terminal S6/AI2 is to be substituted where terminal AI2
and S6 is referenced separately for 1 - 2 HP models and 3 75 HP models prior to version 1.3 unless
otherwise noted.

Table of Contents

Related product manuals