N3 Drive Operations Manual
b (Basic) Parameter Details; b015 b016 33
b015
DC Bus Voltage Display
Selection
0000: Disable Bus Voltage Display
0001: Enable Bus Voltage Display
b016
PID Feedback Display
0000: Disabled
0001: Enable
1.) The keypad displays the PID feedback value when:
· A140=0001 (PID is enabled)
· Parameter A049 = 0020 (Terminal AI2 is PID analog feedback).
· b016=0001 (Displays AI2 as PID analog feedback *value 0 -100)
*If the feedback signal is 0 10V the display value = (AI2 / 10V) x100
*If the feedback signal is 0 20mA the display value =(AI2 / 20mA) x100
2.) Press the DSP key to toggle between the output frequency and PID feedback value.
3.) The inverter displays XXXF when in Run mode, and XXXr when stopped.
NOTES: