N3 Drive Operations Manual
A (Advanced) Parameter Summary; A157 A163 45
Parameter
No.
LCD Display
Description
Range/Code
Factory
Setting
Remarks
A157
Unit : NONE
Engineering Unit
(only for PID
Feedback used
for LCD type)
0000 : NONE
0001 : FPM (feet per minute)
0002 : CFM (cubic feet per minute)
0003 : PSI (pounds per square inch)
0004 : GPH (gallons per hour)
0005 : GPM (gallons per minute)
0006 : in
0007 : ft
0008 : /s (units per second)
0009 : /m (units per minute)
0010 : /h (units per hour)
0011 :Deg F
0012 : inW (inches in water column)
0013 : HP
0014 : m/s (meters per second)
0015 : MPM (meters per minute)
0016 : CMM (cubic meters per
minute)
0017 : W
0018 : kW
0019 : m
0020 : Deg C
0021 : %
0022 : rpm
0000
A158
PID Fdbk Dsp
Max
PID Feedback
Display Unit Max
0-9999
1000
Only for LCD
keypad
A159
PID Fdbk Dsp
Min
PID Feedback
Display Unit Min
0-9999
0
Only for LCD
keypad
A160
Reserved
Reserved
A161
Comm Error
Operation Sel
Communications
time-out
operation
selection
0000: Deceleration to stop.
(b008: Deceleration time 1)
0001: Coast to stop.
0002: Deceleration to stop.
(A026: Deceleration time 2)
0003: Continue operating.
0000
7
A162
Comm Error
detection time.
Communications
time-out
detection
time.
00.0 - 25.5 Sec.
00.00
7
A163
Se Comm Adr
Assigned
Communication
Station Number
1 - 254
1
2
Cont.

Table of Contents